Why Are the Maximum Glass Spans Different Between Skyforce-Top and Skyforce-Side?

One of the most common technical questions we receive about the Skyforce Juliet balcony system is:

“Why can Skyforce-Top span up to 3000mm, but Skyforce-Side is limited to 2600mm?”

At first glance the systems appear very similar – both support frameless toughened laminated glass panels and achieve the same minimalist appearance externally.

The difference in maximum glass spans does not come from a fundamental structural weakness in one system compared to the other.

Instead, it comes down to how each system was originally tested and certified.

Overview of the Skyforce Fixing Options #

Within the Skyforce Juliet balcony range, there are currently two primary fixing configurations.

Skyforce-Top #

(also referred to as face-fixed or fascia-mounted)

The aluminium vertical bars are mounted directly onto the external, front face of the building structure.

Skyforce-Side #

(also referred to as reveal-fixed or recessed mounted)

The mounting bars are installed within the structural reveal or side wall of the opening.

Both systems:

  • Use toughened laminated glass
  • Provide full-height frameless guarding
  • Are tested to BS 6180 horizontal line load requirements

However, the certified maximum glass spans differ.

SystemMaximum Certified Span *
Skyforce-TopUp to 3000mm
Skyforce-SideUp to 2600mm

* Exact spans depend on glass thickness and load category.

The reason for this difference lies in the original testing programme for each system.

How Skyforce-Top Was Tested #

Skyforce-Top was the first system developed within the range, and underwent testing across a sliding scale of horizontal line loads.

The test programme covered load categories from approximately 0.36kN through to 3.00kN, using different spans and heights.

For an 1100mm high system, one of the key certified test cases included:

0.74kN horizontal line load using 21.52mm toughened laminated glass.

This load value is significant because:

  • 0.74kN/m is the typical horizontal line load requirement for Juliet balconies under BS 6180:2011

Because the system was tested at multiple load categories, it allowed certification of larger glass spans where lower load requirements apply.

This is how the 3000mm maximum span was established for Skyforce-Top.

How Skyforce-Side Was Tested #

Skyforce-Side was introduced later as an alternative fixing method.

However, this system was tested independently from Skyforce-Top, and the testing programme took a different approach.

Rather than testing across multiple load categories, the system was tested at one load case only:

1.50kN horizontal line load

Why this load case was chosen remains something of a mystery. Somewhere in the distant past a decision was clearly made to test the system at 1.50kN only, and the reasoning behind it has unfortunately been lost to time.

What we do know is that this load level is significantly higher than the 0.74kN horizontal line load typically required for Juliet balconies under BS 6180:2011.

From a testing perspective, applying a higher load means the system must resist greater force acting on the glass barrier. To achieve this, the certified maximum span of the glass panels must reduce.

As a result, the certified span for Skyforce-Side is limited to 2600mm, even though the typical design load for Juliet balconies is considerably lower.

In simple terms:

  • The published limit reflects the test conditions rather than the typical application
  • The system was tested against a higher load requirement
  • Higher loads require shorter certified spans

Does This Mean Skyforce-Side Is Weaker? #

No.

The reduced certified span does not necessarily mean the system is structurally weaker.

It simply reflects the load level used during the certification process.

If a system is tested against a higher horizontal line load, the allowable span will naturally reduce in order to meet that requirement.

In practical terms:

  • Skyforce-Top was tested across multiple load categories, allowing optimisation of spans
  • Skyforce-Side was tested at a single, higher load category

The certified limits therefore reflect the testing methodology rather than a fundamental difference in structural capability.

Why We Must Always Work to Certified Test Data #

In structural glazing applications, design decisions must always be based on:

  • third-party accredited test evidence
  • documented load classifications
  • published certification limits

Even if engineering judgement suggests that a system could perform similarly at lower loads, compliance must always be based on verified test results.

For that reason we always recommend specifying Skyforce systems strictly within their certified span tables.

Future Testing Plans for the Skyforce Range #

To simplify specification and remove confusion between fixing options, we are planning a future retesting programme across the Skyforce range.

This programme is expected to include:

  • Skyforce-Top
  • Skyforce-Side
  • Skyforce-Slim (our newest version with a slim-profile mounting system)

The goal is to:

  • Test all systems against consistent load categories
  • Align maximum glass spans by glass thickness
  • Produce clear, uniform span tables across the entire Skyforce family

This will make specification easier and ensure direct comparability between fixing types.

Summary #

The difference in maximum glass spans between Skyforce-Top and Skyforce-Side comes down to:

  • Different historical testing programmes
  • Different certified horizontal line loads

It is not a reflection of safety, quality, or system reliability.

When designing Juliet balconies, always ensure that the selected system is specified within the limits of its certified test data and relevant standards.

If you need assistance selecting the correct Skyforce configuration for your project, our technical team will be happy to help.